Order No: CKS7 331-7 KF 02-0AB0
8-channel analog input, full-function temperature measurement module, resolution of 16 bits;
External mechanical range switch can greatly improve the stability of the measurement;
Strong anti-interference ability, stable performance;
Current input with overcurrent protection.
technical parameter
|
|
• rating |
24V DC |
|
Power loss |
Bus consumption current |
100mA |
|
|
L + consumption current |
25mA |
|
|
• total power consumption |
1W |
|
|
• supply current |
Maximum of 60 mA per channel |
|
|
• short-circuit protection |
have |
|
analog input channel |
8 |
|
|
Cable length (shield) |
200m; 50m maximum at 80 mV |
|
|
Input the type and scope |
• voltage |
±80mV,±250mV,±500mV,±1v ,±2.5v ,±5v,1~5V ,±10v |
|
|
The four wire current |
±3.2mA,±10mA,±20mA,4~20mA |
|
|
The second line current |
4~20mA |
|
|
• resistance |
600Ω, 300Ω,150Ω |
|
|
The pyrene thermoelectric coupling |
K,J, N, E,L |
|
|
• hot resistance |
Pt100、Ni100
|
|
A/D conversion accuracy |
16 The |
|
|
Basic transition time per channel |
0.5ms/12.5ms/25ms/100ms |
|
|
Interference inhibition frequency |
40/60/30/10Hz |
|
|
Error (permissive limit in the entire temperature range) |
• voltage |
±0.6% |
|
|
• current |
±0.6% |
|
|
• resistance |
±0.6% |
|
|
• accuracy |
±1℃ |
|
terminal |
Disruption of diagnosis of uterine disease |
Yes, each set can set the parameters |
|
|
Ultraviolet limit values were interrupted |
Yes, you can set the parameters |
|
insulate |
Between the uterine cavity |
not have |
|
|
Between the channel and the backplane bus |
have |
|
Front connector |
20 Needles |
|
|
Size (length X, width X, height) |
40×125×120 |
|
hookup

Contact: FU Bin
Phone: 18072812386
Tel: 0731-85203816
Email: market@cksky.com.cn