ENET-SC Feature Features:
1. Realize the conversion of ModbusRTU serial protocol and ModbusTCP Ethernet protocol, non-transmission transmission;
2. Support the full-duplex asynchronous communication mode, with high efficiency and fast speed;
3. Compatible with semi-duplex communication mode, with a wide range of application;
4. Support 6 upper-level computer simultaneous communication;
5. Support all kinds of upper computer software and touch screen, and access device data through ModbusTCP;
6, the serial port supports RS232 / 485 interface mode, communication port reuse, the port rate is optional 9600bps~115200bps;
7. Support for data communication with Schneider PLC through programming in high-level languages (such as VB, VC, C #, etc.);
8. Special parameter configuration and test tools;
9. Support WEB web page parameter configuration and firmware upgrade.
Typical application
technical parameter:
|
product model |
ENET-SC |
|
description |
The Schneider PLC Ethernet communication processor |
|
pigment |
Metal black |
|
situation display |
Pwr,COM1,COM2,Link |
|
Ethernet interface interface type transmission speed Protocol support TCP linker number |
IEEE 802.3 compatible, Link / Active indicator light, line order adaptive, support Auto-MDIX RJ 45 female socket 10/100Mbps ModbusTCP 6 |
|
X1 interface interface type transmission speed Protocol support |
terminal RS485, RS232 are optional 9.6K~115.2Kbps Modbus RTU/ASCII |
|
X2 interface interface type transmission speed Protocol support |
terminal RS485, RS232 are optional 9.6K~115.2Kbps Modbus RTU/ASCII |
|
configuration software OPC software |
Kunlun state, configuration king, three-dimensional force control, etc KepWare OPC |
|
Diagnostic and parameter settings |
IE Browser, default 192.168.1.178, BCDevice |
|
power supply mode Voltage type |
External to 24VDC 24VDC/100mA |
|
working temperature |
0~60℃ |
|
Working humidity |
90% Non-condensation |
|
way to install |
35mm guide rail installation |
|
electromagnetic compatibility |
2014/30/EU |
|
Anti-vibration |
4.5mm/30Hz/10Min |
|
ESD |
6KV |
|
Factory aging |
The 60 degree aging box operated for 168 hours and was power off 500 million times |
|
Communication stability |
Continuous 30 days of uninterrupted communication with PLC, 130 million communication 0 error |
|
attestation |
CE attestation |
|
Dimensions (L * W * H) |
90*24*65mm |
|
weight |
100g |